User Tools

Site Tools


sensors:tiltmeter

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
Next revision Both sides next revision
sensors:tiltmeter [2012/09/10 17:00]
karina
sensors:tiltmeter [2013/10/21 13:58]
claes [Software]
Line 1: Line 1:
 ====== PNI TCM-XB ForceFieldsensor ====== ====== PNI TCM-XB ForceFieldsensor ======
-This Tiltmeter from the company [[http://www.pnicorp.com/|PNI]] and the sensor is the [[http://www.pnicorp.com/products/fieldforce-tcm|fieldforce-tcm]]. All information is copied from the homepage of the company.+This Tiltmeter from the company [[http://www.pnicorp.com/|PNI Sensor Corporation]] and the sensor is the [[http://www.pnicorp.com/products/fieldforce-tcm|fieldforce-tcm]]. All information is copied from the homepage of the company. 
 + 
 +{{:sensors:pni_tcm.jpg?200|}}
  
  
 box, usb-rs232 converter, usb-plug + cap, sensor box, usb-rs232 converter, usb-plug + cap, sensor
  
 +===== Documentation =====
 +|User manual| {{:sensors:tcm_user_manual_r05.pdf|Download}}|
 +|Data sheet|{{:sensors:tcmxbandmb_datasheet.pdf|Download}} |
 +
 +===== Software =====
 +{{:sensors:tcm_studio_ver_3_0.msi|TCM Studio 3.0}}
 +
 +{{:sensors:tcmtest.zip|}}
 +===== Links =====
  
  
Line 14: Line 25:
  
 http://answers.ros.org/question/10546/pni-digital-compass-driver/#16791 http://answers.ros.org/question/10546/pni-digital-compass-driver/#16791
 +
 +===== PRODUCT Specifications =====
 +
 +==== Performance Specifications (1*) ====
 +
 +^**Parameter**^^^^**Value**^
 +|Heading|Accuracy|≤65° of tilt after full range calibration||<0.3° rms|
 +| ::: | ::: |≤80° of tilt after full range calibration||<0.5° rms|
 +| ::: | ::: |≤5° of tilt after 2D calibration||<2.0° rms|
 +| ::: | ::: |≤2 times the calibration tilt angle after limited-tilt calibration (2*)||<0.2° rms|
 +| ::: |Resolution|||0.1°|
 +| ::: |Repeatability|||0.05° rms|
 +|Tilt (Pitch & Roll)|Range|Pitch||± 90°|
 +| ::: | ::: |Roll||± 180°|
 +| ::: |Accuracy|Pitch||0.2° rms|
 +| ::: | ::: |Roll|≤65° of pitch|0.2° rms|
 +| ::: | ::: | ::: |≤80° of pitch|0.4° rms|
 +| ::: | ::: | ::: |≤86° of pitch|1.0° rms|
 +| ::: |Resolution|||0.01°|
 +| ::: |Repeatability|||0.05° rms|
 +|Maximum Operational Dip Angle (3*)||||85°|
 +|Magnetometers||Calibrated Field Range||± 125 μT|
 +| ::: ||Resolution||0.05 μT|
 +| ::: ||Repeatability||± 0.1 μT|
 +
 +(1*) Specifications are subject to change. Assumes the TCM is motionless and the local magnetic field is clean relative to the calibration. \\
 +(2*) For example, if the calibration was performed over ±10° of tilt, then the TCM would provide <2° rms accuracy over ±20° of tilt.\\
 +(3*) Performance at maximum operational dip angle will be somewhat degraded.
 +
 +==== Operating Characteristics ====
 +
 +=== I/O Characteristics ===
 +
 +^Parameter^^Value^
 +|Communication Interface|TCM XB|Binary RS232 UART|
 +| ::: |TCM MB|Binary CMOS/TTL UART|
 +|Communication Rate||300 to 115200 baud|
 +|Maximum Sample Rate (1*)||≈30 samples/sec|
 +|Time to Initial Good Data (2*)|Initial power up|<210 ms|
 +| ::: |Sleep mode recovery|<80 ms|
 +
 +
 +(1*) The maximum sample rate is dependent on the strength of the magnetic field, and typically will be from 25 to 32 samples/sec.\\
 +(2*) FIR taps set to "0".
 +
 +=== Power Requirements ===
 +^Parameter^^^Value^
 +|Supply Voltage|TCM XB||3.6 to 5 VDC (unregulated)|
 +|:::|TCM MB||3.3 to 5 VDC (unregulated)|
 +|Average Current Draw|TCM XB|@ max. sample rate|20 mA typical|
 +|:::|:::|@ 8 Hz sample rate|16 mA typical|
 +|:::|TCM MB|@ max. sample rate|17 mA typical|
 +|:::| ::: |@ 8 Hz sample rate|13 mA typical|
 +|Peak Current Draw|During application of external power||120 mA pk, 60 mA avg over 2 ms|
 +|:::|During logical power up/down or Sync Trigger||100 mA pk, 60 mA avg over 4 ms|
 +|Sleep Mode Current Draw|||0.3 mA typical|
 +
 +
 +
 +
 +=== Environmental Requirements ===
 +^Parameter^Value^
 +|Operating Temperature (1*)|-40C to +85C|
 +|Storage Temperature|-40C to +85C|
 +
 +(1*) To meet performance specifications, recalibration may be necessary as temperature varies.
 +===== TCM Pin Descriptions =====
 +^Pin number^   TCM XB    ^^
 +^:::^9 pin connector^Pigtailed cable wire color^
 +|1|GND|Black|
 +|2|GND|Grey|
 +|3|GND|Green|
 +|4|NC|Orange|
 +|5|NC|Violet|
 +|6|NC|Brown|
 +|7|UART Tx|Yellow|
 +|8|UART Rx|Blue|
 +|9|+5 VDC|Red|